• Model:ACOAS-ADS-VFC

ACOAS-ADS-VFC - Automatic Duty Share Changeover panel

£ 143.00 (excl. VAT)

£ 171.60 (inc. VAT)

The ACOAS changeover panels are designed to suit single phase twin fan units with airflow switches. Please note that an airflow switch must be fitted to monitor each fan and the airflow switches must not “see” the airflow from the other fan I.E. the 2 airflow switches cannot be in the same airstream.
The control panel fascia has a power lamp, fan fail lamp and a rocker switch. The VFC models have fail contacts that can be used in conjunction with a remote indicator or to interface with a building management system.

Installation:
Check that the auto changeover panel supplied is compatible with the fan motors. Install in a dry sheltered position. Do not install in close proximity to a heat source. Remove the front cover of the controller by unscrewing the fascia fixing screws. This provides access to mounting holes and electrical terminals. All wiring must be carried out by a suitably qualified and competent person and comply with current applicable regulations.

Auto Changeover:
The control panel will automatically changeover from the duty fan to the standby fan if the fuse (within the auto changeover panel) for the duty fan ruptures.
Manual duty share models:
Manual duty share models are fitted with a 2-position (Fan A/Fan B) rocker switch enabling the user to manually select the duty fan. The control panel will auto changeover from the duty fan to the standby fan as described in Auto Changeover above.
Auto duty Share models:
Auto duty share models are fitted with an electronic timer to provide a 12 hour cycle time for each fan.The timer has a jumper link to allow testing of the auto changeover on a 1 minute test cycle for each fan. After testing the jumper link should be fitted back in the 12hr cycle time position. The position of the jumper link for the test cycle and 12 hour cycle are shown below.
Volt free contacts (VFC models)

These models are suffixed with VFC and feature 2 sets of volt free contacts, 1 set for a common fan run status and 1 set for a common fan fail status. The contacts are normally open and close when either fan is running or has failed.
PDF Files


Data Sheet

1 x Helios ZNE Electronic Fan Overrun Timer1 x Push Timer Switch - ZA41 x Time Delay Unit - DT20B2 x MV-B Dual Switch for use with Helios HQW plate fans,3 x Single phase speed controller by auto-transformer - RMB 1.5 Amp1 x Envirovent Silent MV160/100T Mixvent - Timer Model - 100mm - (5 year warranty)1 x ACO8AC/EC AutoChangeover panel1 x ACOAS/ AC/EC Auto Changeover 8Amp1 x CS2 Current Switch3 x Systemair Save Connect 2.0 Internet Module2 x Isolator Switch - ISOSW1 x Helios TSW 1.5 Amp Transformer speed controller1 x S&P MULTI-REG EC FAN CONTROLLER / INTERFACE1 x Elta ACO Panel 149-ACO14E1 x Single phase speed controller by auto-transformer - RMB 10.0 Amp2 x Transformer Speed Control - RTRE- 7.0Amp2 x Elta Variable Speed Drive IP66 - 0.75KW2 x CBM Low Pressure Centrifugal Fan - CBM 10/10 4 Pole 550watt CVR1 x EC-Vent control board2 x Isolator Switch - EFF-ISO2 x WS - Reversing Switch from Helios Fans2 x COM-31 x U-EK plastic housing IP65 - for use with the U-EK230E Motor Protection1 x Duct Termination with Mesh - 355mm2 x TG-R room temperature sensor1 x Elta ACO Panel 149-ACO18B1 x EC-Vent Room Unit1 x Vent Axia Silent 100T (TIMER)1 x Speed Controller - REB101 x MTP 10, 10K, Speed control1 x EM30-24 Electro-Mechanical Control Panel1 x CBM Low Pressure Centrifugal Fan - CBM 10/10 4 Pole 550watt VR1 x EM30-24 Control Panel Commissioning Service1 x Elta 6 Amp Electronic single phase speed controller.2 x MWS 1.5 – Transformer Controller With Motor Protection1 x Round ceiling diffuser 250mm
Reviews
EM 250-E2M 01- Etamaster-250
EM 250-E2M 01- Etamaster-250
£ 128.80

Really well made but comes with no speed controler? ?and can...