Information & frequently asked questions


Fans
Fans used for ventilation and air movement work by one of two different methods. The most common is the axial or propeller fan, similar to those used on stands for moving air in a room or used in computers for cooling power supplies. They can move large volumes of air at very low pressures.
The other type is a centrifugal unit, and these are similar to a centrifugal water pump. They have a plate with radial vanes and the air is forced out by the centrifugal force. These are either an in- line fan, where the air goes straight through parallel to the fan shaft, or the other type is the "squirrel cage" fan where air is drawn into the centre of the fan and exhausted through the side casing, perpendicular to the impeller axis. The latter is rarely used in domestic fans.
Axial fans are the most common, as they are the cheapest to produce and more compact. One disadvantage they have is that they cannot develop high pressures, with a limit around 60Pa-80pa for household sizes.
Centrifugal fans with the same size inlets as axial fans can develop pressures up to 4 times that of an equivalent axial fan, however, they also usually cost a minimum of twice that of an equivalent axial fan. Fans can either be surface mounted or in-duct, where it is in the middle of a duct run.

Fan Curves On a few fans, we show a graph of airflow vs static pressure (back pressure, sort of). This means that if you have a certain pressure that the fan is pushing or pulling against, then you know the likely airflow rate.

Please click HERE for more details on fan curves.

Ducting The usual materials for ducting are either a steel spiral sheetmetal rigid pipe or a flexible PVC or aluminium foil tube supported by spiral steel wire. The latter is easiest to install and is cheap, however it is very restrictive to airflow. The steel pipe requires special tools to be installed properly, which most homeowners or plumbers do not have. The most common fault is to chose ducting which is undersized for the fan capacity, and this increases the noise of the system through the higher air velocity and also increases the friction in the system, which makes the fans work harder or require them to be larger than necessary.
Duct sizes should generally be kept as large as possible A small difference in diameter makes a huge difference to the amount of restriction, as the back pressure from friction losses is inversely proportional to the power of 4.

Duct sizing
Let us take the example of an inline fan in the ceiling: If we assume that the peak pressure of the axial fans in a heat and light fan units is around 60Pa and a peak flow rate of 70l/s in free air with a more or less straight to circular curve between the points (see below). (or maybe from the manufacturers data) We also make some other assumptions: The exhaust grille (and intake if it has one) is 10-20Pa pressure loss.
The correctly sized ducting will be 1.5-3.5pa per metre
Each bend of flexiduct is equivalent to 1.5 -2 metres extra duct length
We have 2 bends, an exhaust grille, and an intake grille, as it is part of the fan and hence part of its quoted performance.
The duct length is 3m.
Our pressure loss is 15pa for each grille + ((3m+2*1.5m per bend)*2 Pa per metre) = 30+ 12 =42Pa.
We know look up our fan curve for 42Pa static pressure and read off the amount of air being moved from the bottom axis.
At the very minimum, the duct size should be at least a large as the size of the fan, i.e. a 150mm fan uses 150mm ducting.

Noise Ratings
Most Sound levels are rated in decibels, measured at 3 meters. (Although some manufacturers on their data sheets state dB@ 1.5 meters. In these cases we have converted to @3m by subtracting 6dB.) Be aware that some fans give noise ratings in SOUND POWER LEVELS, also in decibels, which is a different measure and is normally about 21 decibels higher than the Sound Pressure @3m measurement.
An important thing to remember is that they are logarithmic, which means that they do not go up in a linear (straight-line) fashion, rather it is exponential. This means that a (more or less) 10db increase is twice as loud. A 2-3 dB difference is considered to be a just noticeable to most people, although this varies.

The search for the silent/quiet extractor fan.
Many people want to upgrade their current extractor fan with a quiet version, as most cheap bathroom fans are quite noisy. There are a number of options available.
Firstly, it depends on the duct length. If its only a matter of 3-5 meters, the TD range of mixvent fans will suffice. These are a half way house between an axial fan( suitable for short duct lengths) and a centrifugal fan (suitable for long ducting lengths) and and very quiet. Examine the dB readings on the datasheet for comparison with others.
If a more powerful extraction is required, a centrifugal fan is a must. In this case, our range of Acoustic fans are as quiet as you can get. They have sound insulation inside the box to absorb noise. They are also very powerful and easily cleaned and suitable for domestic/industrial applications where sound levels are a problem.
To absorb any noise from the rushing of air, rather than the fan chassis breakout noise itself, use acoustic ducting and/or a silencer at the input/ output. These are just hollow tubes, acoustically designed to absorb the white noise you get at the end of ducting.
Using one of these solutions will normally solve any noise problem.
Generally, the noise is also proportional to the amount of airflow and the fan speed, If you have problems with a noisy fan or are putting a system in:
1/ Mount the fan towards the end of the duct
2/ Use larger ducting to reduce the air velocity, and hence the noise through fittings and grilles
3/ Use a larger fan but turn it slower. This can make a big difference, as the noise varies with the square of the fan tip speed.
4/ Try using "acoustic ducting".

Air changes per hour reqired. (Guide only)
Bathrooms 10 - 15
Bakery 20 - 30
Canteen 8 - 12
Commercial kitchen 30+
Domestic Kitchen (with hood advised) 8-13
Workshop 8 - 10
Fume cupboard 40 - 50
Garage 6 - 8
Spray booth 20 - 50
Warehouse 3 - 6
Workshops 6 - 10
Wet Room/Shower 15-20


Fan sitting in Bathrooms.
Building regs (BS7671 the Requirements for Electrical Installations) state, in section 601 that any devices in Zone 1 of a bathroom must be running on a low voltage, normally 12volts.
This normally means putting the transformer seperate in Zone 3.
ALTHOUGH other building regulations also say anything IPX4 and above (where the second digit of the IP rating is 4 or more) can be used if protected with a 30mA RCD.
Zone 1 is defined as the area around the bathtub or shower basin up to a height of 2.25m above the floor and at a radius of 1.2m from the water outlet.

Cooling Server Rooms. (Using fans not air-conditioners)
We have had many customers inquiring about how to cool a server room using fans. The answer is obvious, LARGE airflow and when calculated correctly, an extract and input fan system can cool a server room for much less money per year than using air conditioning units AND move some useful warm air to other areas needing heating or even better, a heat recovery unit. This saves money and CO2 emissions yet again and contributes to a greener future by using as energy efficient a system, as possible.
Ask for details.


For the technically minded, a very useful residential duct systems design paper. Download HERE.

Building regs compliance guide (2010) HERE

Click HERE to download the Governments Ventilation Building Regs. (Part F)

Excellent guide to kitchen extraction and odour control HERE

Read our WEEE ((Waste Electrical and Electronic Equipment) regulations) policy HERE.

Atex Rated Fans. (Using fans for explosive enviroments.)
Although we offer various Atex rated fans online, we do not specify, so the end user must know what Atex rating they need and whether it is suitable for their application. We take no liability for the use of any Atex fan. There are professional Atex specifiers which will be happy to help and can specify for your needs (and charge accordingly!) but we do not as we are not qualified to do so and will not due to the risk of litigation. It is VERY important to have the correct rating as the risk of explosion when extracting certain solvents can be very high.
If we are given information on the application and the sovents used we can often offer suggestions as to the correct gas group and ignition temperature (and therefore Atex rating) of the fan you need, but the user would have to go away and verify this is correct for their application by research and/or asking a professional Atex specifier. See below for more Atex information.

Guide to Atex Classification
Hazardous area guide
Gas list from IEC-60079-20-1

Use of TP and TK connections on commercial fans.
The thermal protection in motors is an important protective device. They are basically a switch that goes open circuit in the event of an overheat. The device is manufactured into motors due to the possibility of excessive heat caused by things like the following:

1) Overloading
2) High Ambient Temperature
3) Variations in power supply

If an installer fails to connect the thermal protectors they can allow the motors internal temperature to significantly increase beyond the maximum rating of the motor.
If they are used, the motors would be protected and they wouldn’t overheat. The thermal protection serves as an indicator of possible danger to the motor.
Most manufacturers include in the installation instructions that it is advisable to use them, especially if used in kitchens or high temperature enviroments.
If a fan fails under warranty and the TK connections have NOT been used they will often refuse to honour any warranty, as it is an industry standard that thermal protection is connected within all motors. Without thermal protection you are unable to monitor and protect the motor.

The TP connections can be either connected to a suitable speed controller or DOL starter. In some cases the live feed can be fed through the TP connections to switch off the power in the event of an overheat but this means it is not externally resettable(a requirement for all inline cased axials) and will re-start on its own when it has cooled down.


2 x Elta Variable Speed Drive IP66 - 0.37KW (1ph to 3ph)2 x CBMT/Q 250-54 1 HEATER KIT1 x Duct Mounted Filter Box - G4 Grade Panel - 250mm1 x Elta 2 Amp Electronic single phase speed controller.1 x EM30-24 Electro-Mechanical Control Panel1 x CONTROL ECOWATT - Basic1 x Elta ACO Panel 149-ACO18B1 x ACO 149-ACO1/EDV1 x U-EK plastic housing IP65 - for use with the U-EK230E Motor Protection1 x EC-Vent Room Unit1 x Systemair Save Connect 2.0 Internet Module1 x EM30-24 Control Panel Commissioning Service1 x Egg Crate Grille with Dust panel filter 1 inch- 595x5951 x Electronic extractor fan speed controller - FSC 1.51 x Single Deflection Grille 400mm with OBD damper1 x Non Vision 150mm x 150mm (Air Transfer) Grille - With Flange - MILL FINISH1 x Same Day Shipping Surcharge - City Sprint1 x Egg Crate Grille with Dust panel filter 1 inch- 300x3001 x Northern Ireland Pallet Surcharge1 x DPD 12PM Delivery Surcharge1 x Economy Airvent 100mm Fan with Timer1 x Redelivery Charge1 x DPD 10:30AM Delivery Surcharge2 x DV-ROF-V-225 Roof mounted unit1 x Manrose Window Extractor - WF150AP1 x Economy Airvent 150mm Fan With Pullcord & Shutters1 x Manrose T12 TIMER Transformer- T12T1 x Pallet Delivery Surcharge1 x DPD SATURDAY Delivery Surcharge1 x Economy Airvent 150mm Fan1 x Manrose T12 STANDARD Transformer- T12S1 x Economy Airvent 100mm Fan with Timer/Humidistat/Pullcord1 x AL 400 EC 01 AXIALINE - High Performance Long Cased Axial Fan1 x Manrose 150mm - XF150BP1 x Control board kit Smarty 4X P 1.1 F2 Fan 230V1 x AL 450 EC 03 AXIALINE - High Performance Long Cased Axial Fan1 x 18M - 80mm PVC flexible ducting1 x Manrose 150mm - XF150BHP1 x HIMF - Mixed Flow Fan 125mm Inline Fan1 x Maico EN31- Wall Mounted Fan1 x Manrose XF100HTLVT- Clearance1 x Economy Airvent 100mm Fan with Timer & Shutter1 x CTVT/4-400 High Temp Roof Fan - 51369260001 x CRBB/3-160/052M EC 1H0 MP - Radial Impeller - 160mm2 x HIMF - Mixed Flow Fan 100mm Inline Fan1 x Carriage for Scottish Highlands1 x AW Sileo EC Plate Axial Fan - Three Phase - 800mm2 x HQS Bathroom Axial Flow Fan - 125mm1 x AW Sileo EC Plate Axial Fan - Three Phase - 630mm2 x DV-ROF-V-315 Roof mounted unit1 x AW Sileo EC Plate Axial Fan - Three Phase - 710mm1 x CAB-355 ECOWATT Energy Efficient Acoustic Box Fan1 x Capacitor 2uf for use with the EBM A4E range2 x Fresh Air control carbon filter - 125mm1 x AL 355 EC 01 AXIALINE - High Performance Long Cased Axial Fan1 x CAB-400 ECOWATT Energy Efficient Acoustic Box Fan1 x AL 500 EC 01 AXIALINE - High Performance Long Cased Axial Fan2 x Elta - SMT 125 Mixvent Inline Fan - Clearance Stock Line1 x CAB-200 ECOWATT Energy Efficient Acoustic Box Fan1 x CAB-125 ECOWATT Energy Efficient Acoustic Box Fan1 x Direct Delivery Surcharge - Pre 12:001 x CAB-250 ECOWATT Energy Efficient Acoustic Box Fan1 x HRB/6-451/20-BMVPN - Special Offer1 x 3-pin Plug and lead for TD Silent Ecowatt1 x AW Sileo EC Plate Axial Fan - Three Phase - 560mm1 x Direct Delivery Surcharge1 x Elta Unpodded Silencer Melinex 1D-500mm1 x Biflow SB250-CON4-3 - High Temperature Bifurcated Fan1 x Small Centrifugal Fans CBM/2-133/190 185w1 x Manrose 150mm - XF150BTP1 x Helios DDF-200 Roof Cowl1 x Etamaster EM 250 EC 01 inline mix-vent fan1 x Small Centrifugal Fan - CBM/4-160/150-125 W1 x EBM-Papst D3G133-BF05-14 Double inlet1 x Eco-Loft Positive Input Ventilation System - PIV Loft Mounted -EVL-HAS1 x Etamaster EM 250 EC 02 (high Power) inline mix-vent fan1 x Biflow SB250-CON2-3 - High Temperature Bifurcated Fan1 x G2E160−AL19−56 FLUE FAN1 x D2E146-AP47-331 x D2E146-AP47-C11 x Ancillary Pack for SB-Biflow 250 model1 x Small Centrifugal Fan - CBM/4-180/184-150 W1 x Circular Inline Silencers - 600mm - 600mm1 x Lo-Carbon PUREAIR HOME WITH HEATER BOXED ASSY1 x D2E146-HT67-021 x FSAF1000C1DA SILENCER 1070/161 x MEV Spider Additional Spigots1 x Eco-Loft Positive Input Ventilation System - PIV Loft Mounted -EVL-H1 x Eco-Loft Positive Input Ventilation System - PIV Loft Mounted -EVL-HW1 x Small Centrifugal Fans CBM/2-146/180-300 W1 x Helios DDF-400 Roof Cowl1 x FSAF1250C1DA Silencer 1320/201 x Elta Unpodded Silencer 1D-560mm1 x OZEO H ECOWATT 2 - Humidity Adjustable Wholehouse Ventilation1 x Elta Unpodded Silencer 1D-250mm1 x S&P RF4C-160/062 K040 SF-1744 (230V50Hz) VE1 x Helios DDF-400 G Roof Cowl (GREY)1 x OZEO ECOWATT 2 Wired Low Energy Whole House Extract Ventilation Unit1 x EBM-Papst D2E097-BK76-98 Double inlet1 x RCZ 300 - Fibreglass Roof Cowl1 x Additional Colour change for RAW 630 (12-B-29)1 x Positive Input Ventilation System - Wall Mounted Unit c/w Heater1 x Roof Axial Cowl - RAW500 / 5601 x Dektite Combo Pipe Flashing - DC210REC1 x Elta Wall Cowl SWC56/631 x Flat Roof Terminal -OFT 1 - Felt & Asphalt 110mm1 x Elta Podded Silencer 2D- 900mm1 x Flat Roof Terminal -OFT 5 - Bitumen1 x Roof Axial Cowl - RAW400/4501 x Roof Axial Cowl - RAW630 / 7101 x Elta Wall Cowl SWC25/311 x Remote controller FLEX - for VEKO INT1 x FSAF355B2DX Silencer 395/81 x Roof Axial Cowl - RAW2501 x RDS 1 Helios Transformer Controller With Motor Protection1 x OZEO ECOWATT 2 Wireless Low Energy Whole House Extract Ventilation Unit1 x W2S130-AA03-011 x Spiral Ducting 3 Meters - 150mm1 x VEKA INT 2000/15.0-L1 EKO1 x Elta Wall Cowl SWC35/401 x Roof Axial Cowl - RAW3151 x FSAF315B2DX Silencer 355/81 x Ducting T Piece Equal - 150mm1 x FSAF355B1DX Silencer 395/81 x Elta Wall Cowl SWC45/501 x Elta Unpodded Silencer Melinex 2D-560mm1 x Roof Axial Cowl - RAW10001 x Elta Unpodded Silencer 1D-500mm1 x Elta Unpodded Silencer 1D-800mm1 x HPA Heavy Duty Flexible Ducting - HPA300-FD51 x CBA-130 Inlet Flange for CBT-1301 x CBA-80 Inlet Flange for CBT-801 x Soler & Palau - HCBT/4-710/H - IP651 x Elta Podded Silencer 1D- 710mm1 x CBA-60 Inlet Flange for CBT-601 x Elta Unpodded Silencer 2D-500mm1 x HR-500 DP Heat Exchange Unit1 x CBS-160 Outlet Flange for CBT-1601 x AL 1120 Mounting Flange1 x ASF 355-500 inlet flange DVS1 x CBA-160 Inlet Flange for CBT-1601 x Helios GigaBox 560mm GBW 560/4 centrifugal1 x Elta Unpodded Silencer Melinex 2D-1000mm Dia1 x TechSeal 100FR Duct Sealant Cartridge - 100FRS1 x H14 Hepa Portable Air Purifier - PAP 350 CA H14 with Carbon Filter1 x CBS-130 Outlet Flange for CBT-1301 x EnergiSava 210 Low Energy Heat Recovery Unit1 x A Duct Mountable - Double Drilled Fixing Flange (PAIR) - 710mm1 x Multileaf Volume Control Dampers -500/500 Rectangular Flanged1 x Casals Circular Outlet Connection Flange - 5102018031 x IRAB/4 315A N 230V50Hz 355/100 VE - In-Line Duct Fans - 51329333001 x 14500170 - A - Outlet Flange for THLZ FF 4501 x CAD-COMPACT 900 ADVANCED N8 - MVHR unit1 x HCFT/4-710mm plastic impeller plate fan1 x filter pack (set of 2) pt no. 4438891 x A Duct Mountable - Double Drilled Fixing Flange (PAIR) - 355mm1 x DEF-1000-AN1 x Rosenberg DKHM 315-2SB.090.6FAIE-VU671 x Genius Whole house unit -1 x HD Series Control Damper - 1000mm X 1000mm1 x KRJ - 160 Inlet Guard for CBB/CBT fans1 x A Duct Mountable - Double Drilled Fixing Flange (PAIR) - 400mm1 x Spiral Duct Grille Termination - 355mm1 x HR200WK single room heat recovery unit1 x KRJ - 120 Inlet Guard for CBB/CBT fans1 x EX 140A-4C Mounting Kit for 160mm Duct1 x HRB/6-710-30-BPN - Sickle Bladed 710mm Single Phase1 x RSK400 - Back Draught Shutter1 x ERM 18 protection guard - SGM 18 EX1 x AKOR Spare Filter1 x BD7/7 centrifugal M4 0.13Kw1 x Helios HQW-710/6 - IP551 x ZAP 710-63 Plate axial fan1 x G4 extract filter for IDEO HR unit1 x FB050-6EK.4I.V4P 500mm Axial Fan1 x Soler & Palau - HCBT/4-560/H - IP651 x HRB/2-200-BPN1 x AR Sileo 500 Cased Axial Fan Guard - SG AXC/AM/AR 5001 x HQD 710/4/4 Plate Axial Fan (2.2kw)1 x Impeller Side Guard - 800mm1 x GENIOX 11 Internal Mounted Unit1 x Elta SCP710/4/6-3AC - IP551 x Soler & Palau - HCBT/4-800/H - IP551 x KRJ - 225 Inlet Guard1 x Ducting 15 Degree Bend - 1000mm1 x Soler & Palau - HXBR-250 ECOWATT - IP441 x Impeller Side Guard - 560mm1 x HCFT/4-800/H Plastic impeller plate fan - 800mm1 x MELINEX 315mm Circular Inline Silencers -SLU-6001 x F7/G4 supply filter kit for IDEO HR unit1 x KABT/4- 12000/5601 x A Duct Mountable - Double Drilled Fixing Flange (PAIR) - 560mm1 x Impeller Side Guard - 400mm1 x HD Series Control Damper - 3000mm X 1500mm1 x Impeller Side Guard - 315mm1 x SPI-125 C Iris damper1 x SS Series Slimseal 600mmx600mm Damper1 x Ducting 30 Degree Bend - 1000mm1 x Synthetic Air Filter Media - 10mm x 1000mm x 1000mm1 x PVO 200 (2-POLE) Plate Axial fan - With Shutters1 x Elta SCP710/6/8-3AC - IP551 x Soler & Palau - HXTR/6-710/H - IP54 - BFLOW1 x Impeller Side Guard - 630mm1 x HRT/6-710/30-BQ E21 x HCBT-4/500-H - Three Phase 400v Only - 56033228001 x CBT-130N Centrifugal ATEX II 2G Exe II T31 x MUB 100 710EC-Poti - Multibox Acoustic Fan1 x HD Series Control Damper - 2000mm X 1000mm1 x EKHR 280-2SW BCMI1 x HD-LL Series - 100mm with NFA-S2, Multi Voltage Damper Actuator2 x CBT-100 N (230/400V50HZ) LG270-EXDIIBT41 x Metal Inline Fan - VENT-315NK1 x SS Series Slimseal 800mmx800mm Damper1 x Spiral Ducting 3 Meters - 1000mm1 x MELINEX 315mm Circular Inline Silencers -SLU-3001 x RSK450 - Back Draught Shutter1 x Nicotra RDH G2E7-04501 x Helios HQW-250/4 - IP551 x Systemair AW Sileo 710-DS1 x Impeller Side Guard - 710mm1 x FAST-TRACK RANGE 75mm - Valve Adaptor 90° 125mm1 x Soler & palau TCBT/2-250/H - IP441 x Kitchen Extract Kit with Grease Filter and External Wall Fan - High Flow - CEF-4501 x Ducting 90 Degree Bend - 1000mm1 x Soler & Palau - HCBT/4-800/L-AX - IP551 x DEF-800AN1 x HD-LL Series 600x6001 x Helios HQW-200/2 - IP551 x Multiflow SMB550/4-1AC1 x CADB/T-HE PRO-REG Series1 x CBMT/Q 315-54 1 HEATER KIT1 x Raptor SDA250/4-1AC1 x Helios HQW-500/6 - IP551 x CMT-2 120/50 - 0,09Kw - LG270 Single inlet centrifugal fan direct driven1 x Kitchen Extract Kit with Grease Filter and External Wall Fan - Standard - CEF-4501 x Flexible PVC Ducting - 220x901 x HRFD 250/2 EX Atex Rated 250mm Cased Axial Fan 400v1 x MMP Replacement Front Cover - GOLD METAL1 x KRJ - 280 Inlet Guard1 x Soler & Palau - HCBT/4-710/H - BFLOW1 x Elta Turboflow-TF - 630mm - Single phase1 x PVO 200 (2-POLE) Plate Axial fan1 x Anti Vibration Duct Suspension Rings - 150mm1 x HRST/6-800/28-BZ-68 (400V50)C1 x Elta SCP250/4-1AC - IP551 x EX 180A-4 (Three Phase) Centrifugal Fan (ATEX)1 x KD 250 M1 Circular duct fan1 x ERR 31/1 Centrifugal inline fan1 x CBT-100N Centrifugal ATEX II 2G Exe II T31 x FB061-6EK.4I.V4P Axial Fan (124626E)1 x Spiral Ducting 3 Meters - 355mm1 x BDRAX 250-E2 Cased Axial External Rotor Fan1 x Belt Drive Cased Axial Fan - 630mm - L version1 x Ducting Y Piece - 150mm